What is NYC RCNY § 2-09?

Quick Answer

An owner of equipment that is required to have a certificate of operation must perform annual tune-ups and combustion tests. Records of the dates and procedures of each tune-up and results of these tests must be kept by the owner for a minimum of five years and must be submitted within five business days if requested b

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →
Effective: 6/12/2016Last amended: 6/12/2016

§ 2-09 Annual Tune-ups and Record Keeping Requirements.

RCNY § 2-09

An owner of equipment that is required to have a certificate of operation must perform annual tune-ups and combustion tests. Records of the dates and procedures of each tune-up and results of these tests must be kept by the owner for a minimum of five years and must be submitted within five business days if requested by the department.

(a)Annual equipment tune-ups and combustion efficiency test.

(1)The owner of the equipment must commission a tune-up for the equipment and test the combustion efficiency. The tune-up and combustion efficiency test must occur at both high-fire and normal operating conditions.

(i)A qualified combustion tester must perform a combustion efficiency test for each piece of equipment and each oil fired boiler in accordance with 15 RCNY § 2-08(a)(1).

(ii)The tune-up required to increase boiler efficiency must be conducted in accordance with Subpart JJJJJJ of Part 63 of Title 40 of the Code of Federal Regulations and the guidelines outlined by the department. The results of the tune-up must be recorded on a form provided by the department.

(b)Combustion Analyzer Requirements.

(2)The equipment used must conform with the following requirements: Accuracy Resolution Oxygen (O 2 )+ 0.2%0.1%Pressure/Draft+ 2%0.04" water columnTemperature+ 0.5%0.1 °F An optional test using the following standards may be applied as provided in the following chart: Accuracy Resolution Carbon Monoxide (CO)+ 2 ppm at 0.0 to 39.9 ppm+ 5% at 40.0 to 500 ppm0.1 ppmNitric Oxide (NO)+ 5 ppm at 0 - 100 ppm+ 5% 101 - 2,000 ppm1 ppm (3) The following procedure must be followed in the use of the combustion analyzer: (i) Set up the combustion analyzer per manufacturer's instructions. In uncontaminated air (outdoor) start the analyzer and allow unit to complete the zeroing process. Never allow the analyzer to zero in the breeching.

(c)This section applies to registrations that are subject to the requirements of 15 RCNY § 2-01. (Amended City Record 5/13/2016, eff. 6/12/2016)

Common Questions

Our team

Meet the people you will work with

Free case review

Talk to an attorney before you act on NYC code.

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters