What is NYC MC § 909.3?

Quick Answer

This section specifies the placement of vented wall furnaces, requiring that doors cannot swing within 12 inches of an air inlet or outlet measured at right angles. It prohibits the installation of doorstops or closers to achieve this clearance. Applies to building owners installing vented wall furnaces.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

909.3 Door swing.

MC § 909.3

Vented wall furnaces shall be located so that a door cannot swing within 12 inches (304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance.