810.2 Requirement of a smoke test.
MC § 810.2
A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit-holder when the work is performed as part of a limited alteration application, as defined in Section 28-101.5 of the Administrative Code. Such test shall not be required to be witnessed by the department, registered design professional or special inspector. (Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023) Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.