This section outlines the requirements for duct and air transfer opening systems that penetrate fire-resistance-rated floor/ceiling assemblies in certain occupancies. It specifies conditions under which these penetrations are permitted without shaft enclosure protection, including the installation of fire dampers and firestopping measures. Applies to building owners in non-Group I-2 and I-3 occupancies.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

607.6.1 Through penetrations.

MC § 607.6.1

In occupancies other than Groups I-2 and I-3, a duct and air transfer opening system constructed of approved materials in accordance with this code that penetrates a fire-resistance-rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection provided that a listed fire damper is installed at the floor line and the penetration is firestopped or the duct is protected in accordance with Section 714.4 of the New York City Building Code. For air transfer openings, see Item 6, Section 712.1.9 of the New York City Building Code. Exception: A duct serving a dwelling unit is permitted to penetrate three floors or less without a fire damper at each floor provided such duct meets all of the following requirements.

1.The duct is contained and located within the cavity of a wall and is constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage).

2.The duct opens into only one dwelling or sleeping unit and the duct system is continuous from the unit to the exterior of the building.

3.The duct does not exceed a 5 inch (127 mm) nominal diameter and the total area of such ducts does not exceed 100 square inches (64 516 mm 2 ) for any 100 square feet (9.3 m 2 ) of the floor area.

4.The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 or UL 263 time-temperature conditions under a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.

5.Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly are protected with a listed ceiling radiation damper installed in accordance with Section 607.6.2.1.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 607.6.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters