This section outlines the prohibited sources for outdoor or return air in forced-air heating and cooling systems. It specifies various locations from which air cannot be taken, including areas near appliance vents, hazardous locations, and certain rooms like kitchens and bathrooms. Applies to building owners operating forced-air systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

618.4 Prohibited sources.

FGC § 618.4

Outdoor or return air for forced-air heating or forced-air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet (914.4 mm) above the outside air inlet.

2.Where there is the presence of objectionable odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway.

3.A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code.

4.A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not apply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space.

5.A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct-vent appliance or an appliance not requiring a vent in accordance with Section 501.8.

6.A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned attic. Exceptions: 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited.

7.A crawl space by means of direct connection to the return side of a forced-air system. Transfer openings in the crawl space enclosure shall not be prohibited.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 618.4?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters