What is NYC MC § 605.5?

Quick Answer

This section mandates that all air filters in HVAC systems be maintained free of excess dust and combustible materials. Filters must be renewed or cleaned based on airflow resistance criteria. Additionally, systems with airflow of 4000 cfm or more require a draft gauge or pressure transmitter. Applies to building owners managing HVAC systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

605.5 Filter maintenance.

MC § 605.5

All air filters shall be kept free of excess dust and combustible material. Unit filters shall be renewed or cleaned when the resistance to airflow has increased to two times the original resistance or when the resistance has reached a value of recommended replacement by the manufacturer. A permanently installed draft gauge or differential pressure transmitter shall be provided for all systems equal to or greater than 4000 cfm (1.89 m 3 /s).

Common Questions

Our team

Meet the people you will work with

TI

Tiffany Irizarry

Legal Coordinator

OATH / DOB
TI

Tiffany Irizarry

Legal Coordinator

OATH / DOB

Free case review

Have a matter that touches § 605.5?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

reception@nacmiaslaw.com

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters