601.2.1 Corridor ceiling.
MC § 601.2.1
Use of the space between the corridor ceiling and the floor or roof structure above as a return air plenum is permitted for one or more of the following conditions: 1. The corridor is not required to be of fire-resistance-rated construction.
2.The corridor is separated from the plenum by fire-resistance-rated construction.
3.The air-handling system serving the corridor is shut down upon activation of the air-handling unit smoke detectors required by this code.
4.The air-handling system serving the corridor is shut down upon detection of sprinkler waterflow where the building is equipped throughout with an automatic sprinkler system.
5.The space between the corridor ceiling and the floor or roof structure above the corridor is used as a component of an approved engineered smoke control system.