514.2 Prohibited applications.
MC § 514.2
Unless specifically designed or listed for the specific applications and as part of an engineered system, energy recovery ventilation systems shall not be used in the following systems: 1. Hazardous exhaust systems covered in Section 510.
2.Dust, stock and refuse systems that convey explosive or flammable vapors, fumes or dust.
3.Smoke control systems covered in Section 513.
4.Commercial kitchen exhaust systems serving Type I or Type II hoods.
5.Clothes dryer exhaust systems covered in Section 504. Exception: The application of energy recovery ventilation equipment that recovers sensible heat only utilizing coil-type heat exchangers shall not be limited by this section.