What is NYC MC § 508.1.2?

Quick Answer

This section requires design plans for commercial kitchen ventilation systems to include a diagram showing the air balance, including makeup, transfer, exhaust, and infiltration air flow rates. It also stipulates that negative pressurization from the kitchen exhaust must not disrupt operations in connected spaces or exceed door opening force limits. Applies to building owners managing commercial kitchens.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

508.1.2 Air balance

MC § 508.1.2

Design plans for a commercial kitchen ventilation system shall include a schedule or diagram indicating the design air balance of the kitchen and all communicating spaces clearly indicating makeup, transfer, exhaust and infiltration air flow rates. Negative pressurization caused by the kitchen exhaust system shall not cause improper operation of systems in communicating spaces or cause door opening forces in the building to exceed the limits set forth in Chapter 10 of the New York City Building Code.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 508.1.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters