This section outlines the clearance requirements for Type I hoods in commercial kitchens, specifying a minimum distance of 18 inches to combustibles. An exception is provided for certain wallboard materials when specific conditions are met. Applies to building owners installing Type I hoods in their properties.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

507.2.6 Clearances for Type I hood.

MC § 507.2.6

A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457.2 mm). Exception: Clearance shall not be required from gypsum wallboard or 1/2-inch (12.7 mm) or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches (457.2 mm) in all directions from the hood.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 507.2.6?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters