506.4.2 Type II terminations.
MC § 506.4.2
Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's instructions and shall comply with all of the following: 1. Outlets shall terminate not less than 3 feet (914.4 mm) in any direction from openings into the building.
2.Outlets shall terminate not less than 10 feet (3048 mm) from property lines or buildings on the same lot.
3.Outlets shall terminate not less than 10 feet (3048 mm) above grade.
4.Outlets that terminate above a roof shall terminate not less than 30 inches (762 mm) above the roof's surface.
5.Outlets shall terminate not less than 30 inches (762 mm) from exterior vertical walls.
6.Outlets shall be protected against local weather conditions.
7.Outlets shall not be directed onto walkways.
8.Outlets shall meet the provisions for exterior wall opening protectives in accordance with the New York City Building Code.