What is NYC MC § 506.3.2.2?

Quick Answer

This section outlines the requirements for duct-to-hood joints, specifying that they must be constructed with continuous liquid-tight welded or brazed joints that are smooth and accessible for inspection. Exceptions are provided for specific types of connections that meet detailed criteria. Applies to building owners involved in the installation of duct systems in commercial kitchens.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

506.3.2.2 Duct-to-hood joints.

MC § 506.3.2.2

Duct-to-hood joints shall be made with continuous internal or external liquid-tight welded or brazed joints. Such joints shall be smooth, accessible for inspection, and without grease traps. Exceptions: This section shall not apply to: 1. A vertical duct-to-hood collar connection made in the top plane of the hood in accordance with all of the following: 1.1. The hood duct opening shall have a 1-inch-deep (25.4 mm), full perimeter, welded flange turned down into the hood interior at an angle of 90 degrees (1.57 rad) from the plane of the opening. 1.2. The duct shall have a 1-inch-deep (25.4 mm) flange made by a 1-inch by 1-inch (25.4 mm by 25.4 mm) angle iron welded to the full perimeter of the duct not less than 1 inch (25.4 mm) above the bottom end of the duct. 1.3. A gasket rated for use at not less than 1,500°F (815.6°C) is installed between the duct flange and the top of the hood. 1.4. The duct-to-hood joint shall be secured by stud bolts not less than 1/4 inch (6.4 mm) in diameter welded to the hood with a spacing not greater than 4 inches (101.6 mm) on center for the full perimeter of the opening. The bolts and nuts shall be secured with lockwashers.

2.Listed and labeled duct-to-hood collar connections installed in accordance with Section 304.1.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 506.3.2.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters