What is NYC MC § 313.3.1.2?

Quick Answer

This section outlines the requirements for supporting boiler breeching and piping when mechanical draft fans are used. The statute specifies that such piping must be supported for a distance of 50 pipe diameters on resilient isolators, each with a minimum static deflection of 1 inch. Applies to building owners with mechanical boiler systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

313.3.1.2 Boiler breeching and piping.

MC § 313.3.1.2

When boilers are equipped with mechanical draft fans, the boiler breeching and piping that are supported from or on slabs, floors or walls that are contiguous to the dwelling unit shall be supported for a distance of 50 pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of 1 inch (25.4 mm).