What is NYC MC § 1305.7.9?

Quick Answer

This section outlines requirements for tanks on any floor that are served by pumps, specifying that the normal vent must connect to the overflow pipe and be piped at least 8 feet above it, terminating outdoors. It mandates the installation of a liquid sensor to shut down the oil supply during an overflow. Applies to building owners with such tank installations.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1305.7.9 Tanks served by pumps.

MC § 1305.7.9

For tanks on any floor served by pumps, the normal vent shall be connected to the overflow pipe, shall be piped a minimum of 8 feet (2438.4 mm) above the overflow pipe and terminated directly to the outdoors. A liquid sensor shall be installed in the vent of the remotely served tank in order to shut down oil supply in the event of an overflow.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1305.7.9?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters