This section outlines the requirements for overflow piping in fuel oil storage systems installed above the lowest floor. It specifies that the overflow piping must be gravity-fed into the top of the tank at the lowest floor, with certain size and installation criteria. Applies to building owners with fuel oil storage tanks.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1305.3.8 Overflow piping.

MC § 1305.3.8

In systems with fuel oil storage tanks above the lowest level, overflow piping from tanks installed above the lowest floor shall be piped by gravity into the top of the tank at the lowest floor that supplies fuel to such tank. The overflow pipe shall be minimum two pipe sizes larger than fuel oil supply pipe. Valves shall not be installed on overflow piping.