1305.16.1 Replacement of tanks in prior code buildings.
MC § 1305.16.1
Replacement of tanks in prior code buildings may utilize an existing gravity ventilation system complying with the following: 1. The total net free area of supply and exhaust openings shall be equal to at least 1 percent of the floor area of the room, equally divided between the supply and exhaust; and 2. Independent supply and exhaust openings to the outside; or 3. Independent supply and exhaust ducts to the outside.