1210.5 Fittings.
MC § 1210.5
Ground-source heat pump pipe fittings shall conform to the standards listed in Table 1210.5 and, if installed underground, shall be suitable for burial. Table 1210.5Ground-Source Loop Pipe Fittings MaterialStandard (see Chapter 15)MaterialStandard (see Chapter 15)Chlorinated polyvinyl chloride (CPVC)ASTM D 2846; ASTM F 437; ASTM F 438; ASTM F 439; CSA B137.6Cross-linked polyethylene (PEX)ASTM F 877; ASTM F 1807; ASTM F 1960; ASTM F 2080; ASTM F 2159; ASTM F 2434; CSA B137.5Polyethylene/aluminum/polyethylene (PE-AL-PE)ASTM F 1282; ASTM F 2434; CSA B137.9High Density Polyethylene (HDPE)ASTM D 2683; ASTM D 3261; ASTM F 1055; CSA B137.1; CSA C448; NSF 358-1Polypropylene (PP-R)ASTM F 2389; CSA B137.11Polyvinyl chloride (PVC)ASTM D 2464; ASTM D 2466; ASTM D 2467; CSA B137.2; CSA B137.3Raised temperature polyethylene (PE-RT)ASTM D 3261; ASTM F 1807; ASTM F 2159; CSA B137.1