1106.5.1 Refrigeration system emergency shutoff.
MC § 1106.5.1
A clearly identified switch of the break-glass type or an approved tamper-resistant switch shall provide off-only control of refrigerant compressors, refrigerant pumps, and normally closed, automatic refrigerant valves located in the machinery room. Additionally, this equipment shall be automatically shut off whenever the refrigerant vapor concentration in the machinery room exceeds the vapor detector's upper detection limit or 25 percent of the LEL, whichever is lower.