This section mandates that the lowest pressure zone in a refrigerating system must have a dedicated means to detect pressure increases approaching the relief device setpoint. Upon activation of the overpressure sensing device, all compressors in the affected system must stop operating. Applies to property operators managing refrigerating systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1105.9.2.2 Overpressure in low-pressure zone.

MC § 1105.9.2.2

The lowest pressure zone in a refrigerating system shall be provided with a dedicated means of determining a rise in system pressure to within 15 psi (103.4 kPa) of the zone pressure relief device setpoint. Activation of such overpressure sensing device shall cause all compressors on the effected system to immediately cease operation.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1105.9.2.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters