What is NYC MC § 1105.6.1?

Quick Answer

This section outlines the requirements for the discharge location of exhaust from mechanical ventilation systems. The statute mandates that exhaust must be directed outdoors, maintaining specific distances from outdoor air intakes and fire escapes. Applies to building owners managing mechanical ventilation systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1105.6.1 Discharge location.

MC § 1105.6.1

The discharge of the air shall be to the outdoors in accordance with Chapter 5. Exhaust from mechanical ventilation systems shall be discharged not less than 20 feet (6096 mm) from outdoor air intake or openings into buildings and 10 feet (3048 mm) from a fire escape or exterior stair.