What is NYC MC § 1105.10?

Quick Answer

This section mandates the installation of clearly identified break-glass switches for controlling compressors and ventilation fans in machinery rooms. The switches must be placed outside each entrance to the machinery room, or immediately inside if impractical, ensuring accessibility at all times. Applies to building owners with machinery rooms.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1105.10 Remote control.

MC § 1105.10

A clearly identified switch of the break-glass type shall provide off-only control of the compressors in the machinery room. A second clearly identified switch of the break-glass type shall provide on-only control of the machinery room ventilation fans. Such switches shall be located outside each entrance to the machinery room and as close to the entrance as practicable, except that when an outside location is impracticable, such switches may be located immediately inside the machinery room provided such location is accessible at all times.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1105.10?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters