This section establishes that the amounts specified in Table 1103.1 are reduced by 50 percent for institutional occupancies, excluding kitchens, laboratories, and mortuaries. It also sets a limit of 550 pounds for Group A2, B2, A3, and B3 refrigerants in occupied areas or machinery rooms. Applies to building owners managing institutional facilities.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1104.2.1 Institutional occupancies.

MC § 1104.2.1

The amounts shown in Table 1103.1 shall be reduced by 50 percent for all areas of institutional occupancies except kitchens, laboratories and mortuaries. The total of all Group A2, B2, A3 and B3 refrigerants shall not exceed 550 pounds (249.4 kg) in occupied areas or machinery rooms. Nothing in this section shall be construed to allow the use of Group A3 and B3 refrigerants if otherwise prohibited.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1104.2.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters