What is NYC FGC § 409.6?

Quick Answer

This section mandates that laboratories with multiple fuel gas outlets must have a dedicated shutoff valve accessible within the laboratory space. The valve should be located near the egress door and marked with signage stating 'Gas Shutoff.' Applies to educational, research, commercial, and industrial laboratory spaces.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

409.6 Shutoff valve for laboratories.

FGC § 409.6

Where provided with two or more fuel gas outlets, including table-, bench- and hood-mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through which all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating "Gas Shutoff."

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 409.6?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters