§ 8-04 Process Control Measures.
RCNY § 8-04
All records required pursuant to this section must be retained and produced in accordance with subdivision (a) of 24 RCNY § 8-07.
(a)Routine system monitoring. An owner must designate a responsible person as defined in 24 RCNY § 8-02 to monitor each cooling tower system at least weekly while such system is in use.
(1)The responsible person must enter on a written or electronic checklist provided and maintained by the owner all visual observations of the cooling tower system and associated equipment.
(2)The responsible person must possess the skills and have the knowledge necessary to be able to monitor the system under the guidance of a qualified person, in accordance with the management program and plan.
(3)All wetted surfaces visible during cooling tower operation without shutting down the system, tower basins and drift eliminators must be observed during monitoring and the presence of organic material, biofilm, algae, scale, sediment and silt/dust deposits, organics (oil and grease), and other visible contaminants observed must be noted on the checklist.
(4)The responsible person must observe and note the condition of chemical dosing and control equipment and the bleed-off system, and determine if there is sufficient storage and delivery of treatment chemicals.
(5)Any system anomalies or problems must be recorded on the checklist and reported to the management and maintenance team for corrective action to be completed within 24 hours.
(b)Compliance inspections. An owner must retain a qualified person to conduct a compliance inspection at least once every ninety (90) days while a cooling tower system is in operation. The qualified person must complete and the owner must maintain a written or electronic checklist containing observations and findings with respect to any of the following: (1) Presence of organic material, biofilm, algae, and other visible contaminants.
(6)Review of routine maintenance records to ensure proper implementation of required activities and corrective actions as needed.
(c)Maintenance.
(d)Cleaning. The cooling tower system must be cleaned whenever routine monitoring indicates a need for cleaning, but no less than twice a year, in accordance with the maintenance program and plan. Cleaning protocol indicated by the manufacturer's instructions or industry standards, and worker protective measures, as required by applicable law must be specified in the maintenance program and plan. Water contact areas such as the basin, sump, fill, spray nozzles and fittings, drift eliminators and air intake louvres must be properly accessed or removed to facilitate cleaning.
(e)Aerosol and mist control. The cooling tower system must be operated at all times to minimize the formation and release of aerosols and mist. Owners must install and maintain drift eliminators in accordance with the manufacturer's specifications and the New York City Construction Codes. The calculated drift loss at maximum design water circulation must not exceed the manufacturer's tested value for maximum drift loss. Counter-flow cooling towers must achieve a reduction of drift loss to no more than 0.002% percent of the recirculated water volume; cross-flow cooling towers must achieve a reduction of drift loss to no more than 0.005% of the recirculated water volume.
(f)Summertime hyperhalogenation.













