This section outlines the requirements for cross connections in standpipe systems, including specifications for riser connections, valve installations, and pipe sizes. The Department of Buildings enforces these regulations. Applies to building owners with standpipe systems that require multiple risers.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-941 Cross connections.

AC § 27-941

(a)Standpipe systems that include more than one riser shall have all risers cross-connected at, or below, the street entrance floor level, except as otherwise provided in this section.

(b)Standpipe systems in buildings required by the provisions of section 27-943 of this article to have one or more zones shall be so designed and installed that the risers supplied from each zone will be cross-connected below, or in, the story of the lowest hose outlets from the water source in each zone. Horizontal intermediate check valves shall be installed in the run of each riser continuing into a higher zone in such manner as to permit all upper zones of the system to be fed through one riser from the zone below and to prevent any lower zone of the system from being supplied from a zone above.

(c)Risers supplied by an upper level cross connection shall be provided with manual control valves or remote control valves, so arranged that risers supplied by the upper level cross connections may independently be shut off from the tank supplies.

(d)Cross connections shall be at least as large as the largest riser supplied by the cross connection. However, when supplying two, but not more than four four-inch risers, the cross connection shall not be less than five inches. The cross connection shall not be less than six inches for all other riser combinations.

(e)Where there is no cellar, cross connections may be hung from the ceiling of the lowest story.

(f)Each siamese connection shall be connected to a riser or to a cross connection connecting other siamese hose connections or risers. The pipe from the siamese connection to the riser or cross connection shall be five inch i.p.s., except that a four inch pipe shall be sufficient when such pipe supplies a single four inch riser system. The pipe from the siamese connection shall be run as directly as practicable to the riser or cross connection.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 27-941?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters