This section outlines the installation requirements for wood burning appliances, including fireplaces and stoves. It specifies the necessary clearances, location restrictions, and mounting guidelines to ensure safety and proper ventilation. Applies to building owners installing wood burning appliances in residential settings.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-848.08 Wood burning appliances: Installation.

AC § 27-848.08

(a)Scope. Wood burning appliances include factory-built fireplaces, fireplace stoves, room heaters, and fireplace inserts.

(b)Listing. Wood burning appliances shall be listed and accepted and shall be installed in accordance with the terms of their listing and acceptance.

(c)Location of appliances.

(1)Every appliance shall be located with respect to building construction and other equipment so as to permit access to the appliance. Sufficient clearance shall be maintained to permit cleaning of surfaces, the replacement of air filters, blowers, motors, controls and chimney connectors, and the lubrication and servicing of moving parts.

(2)Wood burning appliances shall not be installed in confined spaces or alcoves. The minimum size of the space or room in which the appliance is located shall be three hundred cubic feet. There shall be at least one openable window serving such space or room.

(3)Wood burning appliances shall not be installed in any location where gasoline or any other flammable liquids, vapors or gases are present or likely to be present.

(4)Wood burning appliances shall not be installed in any garage.

(d)Air for combustion and ventilation. Wood burning appliances shall be installed in a location in which the facilities for ventilation permit proper chimney draft and maintenance of safe temperature under conditions of use and provide sufficient air to prevent carbon monoxide from entering the dwelling space. Appliances shall be located so as not to interfere with proper circulation of air within the heated space. Where buildings are so tightly sealed that normal infiltration does not provide the necessary air, outside air shall be introduced.

(e)Mounting for residential type appliances.

(f)Mounting for fireplace stoves and room heaters.

(g)Clearances. Woodburning appliances shall be installed with the following minimum clearances to combustible construction: Above the top of appliance – thirty-six inches; from front – thirty-six inches; from back – thirty-six inches; from sides – thirty-six inches. The minimum clearance to noncombustible construction shall be six inches when table 14-1 herein is used except that forty-eight inches shall be maintained where the fuel is inserted. Accepted stoves shall be exempt from the above-mentioned clearances and shall be installed in accordance with the appropriate reference standard and clearances determined therefrom through tests specified in the reference standard.

(h)Reduction of clearances from wood burning appliances.

(5)All clearances provided between wood burning appliances and combustible materials shall be large enough so as to maintain sufficient clearance between chimney connectors and combustible materials as required in subchapter fifteen of this chapter.

(i)Accessories. Factory-built accessories for wood burning appliances such as heat exchangers, stove mats, floor pads and protection shields shall be listed and accepted, and shall be installed in accordance with the terms of their listing and acceptance. TABLE 14-1 REDUCTION OF APPLIANCE CLEARANCE WITH SPECIFIED FORMS OF PROTECTION 1,2,3,4,5,6,7,8,9,10 Clearance reduction system applied to and covering all combustible surfaces within the distance specified as required clearance with no protectionMaximum allowable reduction in clearance (percent)When the required clearance with no protection is 36 in., the clearances below are the minimum allowable clearance. For other required clearances with no protection, calculate minimum allowable clearance from maximum allowable reduction. 9,10 As Wall ProtectorAs Ceiling ProtectorAs Wall Protector (in.)As Ceiling Protector (in.)(a) 3 1/2 in. thick masonry wall without ventilated air space.33%–24–(b) 1/2 in. thick noncombustible insulation board over 1 in. glass fiber or mineral wool batts without ventilated air space.50%33%1824(c) 0.024 in. (24 gage) sheet metal over 1 in. glass fiber or mineral wool batts reinforced with wire, or equivalent, on rear face with ventilated air space.66%50%1218(d) 3 1/2 in. thick masonry wall with ventilated air space.66%–12–(e) 0.024 in (24 gage) sheet metal with ventilated air space.66%50%1218(f) 1/2 in. noncombustible insulation board with ventilated air space.66%50%1218(g) 0.024 in (24 gage) sheet metal with ventilated air space over 0.024 in (24 gage) sheet metal with ventilated air space.66%50%1218(h) 1 in. glass fiber or mineral wool batts sandwiched between two sheets 0.024 in. (24 gage) sheet metal with ventilated air space.66%50%1218 Notes for Table 14-1:1 Spacers and ties shall be of noncombustible material. No spacers or ties shall be used directly behind appliance or conductor. 2 With all clearance reduction systems using a ventilated air space, adequate air circulation shall be provided. There shall be at least 2 in. between the clearance reduction system and combustible walls and ceilings for clearance reduction systems using a ventilated air space. 3 Mineral wool batts (blanket or board) shall have a minimum density of 8 lb. per ft 3 and have a minimum melting point of 1,500°F. 4 Insulation material used as part of clearance reduction system shall have a thermal conductivity of 1.0(BTU-In.)/(Sq ft-Hr -°F) or less. Insulation board shall be formed of noncombustible material. 5 If a single wall connector passes through a masonry wall used as a wall shield, there shall be at least 1/2 in. of open, ventilated air space between the connector and the masonry. 6 There shall be at least 2 in. between the appliance and the protector. In no case shall the clearance between the appliance and the wall surface be reduced below that allowed in the table. 7 Clearances in front of the loading door and/or ash removal door of the appliance shall not be reduced from those in Section 8-6. 8 All clearances and thicknesses are minimums: larger clearances and thicknesses are acceptable. Clearances are not to be less than 12 in. from appliances. 9 To calculate the minimum allowable clearance, the following formula may be used: C pr = C un x (1-R/100). C pr is the minimum allowable clearance. C un is the required clearance with no protection, and R is the maximum allowable reduction in clearance. 10 Refer to Figures 14-11 and 14-12 for other reduced clearances using materials (a) through (h). Figure 14-6 Figure 14-7 Figure 14-8 Figure 14-9 Figure 14-10 Figure 14-11 Figure 14-12

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 27-848.08?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters