§ 27-521.4 Fire protection equipment.
AC § 27-521.4
(a)Smoke detectors. In all spaces opening onto an atrium, a smoke detecting system shall be installed in accordance with the requirements of reference standard RS 17-5E.
(b)Standpipes. At least one standpipe outlet in addition to a riser or risers within required stairways, shall be installed in every atrium.
(c)Sprinklers.
(1)Every story or mezzanine within an atrium that overhangs another story or mezzanine within fifty feet shall have the overhang sprinklered in accordance with section 27-956 of article four of subchapter seventeen of this chapter, except that atrium ceilings less than fifty feet above the atrium floor but more than thirty feet above the floor may alternatively be provided with smoke detectors, which shall be of the central supervisory type connected to an approved central station. Every room or space opening onto the atrium shall be sprinklered, no matter where located.
(2)Except as otherwise permitted by subdivision (c) of section 27-521.3 of this article, at glass panels permitted by subdivision (d) of such section, sprinklers on the occupied side at all levels shall be spaced six feet apart parallel to the glass and that distance away from the glass panels so as to insure complete glass wetting upon activation. No obstructions to such wetting capability shall be permitted.
(3)Every sprinkler system for an atrium shall be provided with sources of water supply in accordance with article four of subchapter seventeen of this chapter.