This section mandates that gasoline and diesel oil motor vehicle fuel storage tanks be installed below ground and vented to the open air, with specific requirements for their installation and support. The Fire Commissioner is the enforcing agency. Applies to property operators managing fuel storage tanks.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-440 Gasoline and diesel oil motor vehicle fuel storage.

AC § 27-440

All volatile flammable liquids and diesel oil motor vehicle fuel storage tanks shall be installed below ground and vented to the open air except for such aboveground installation as may be authorized by the rules of the fire commissioner. The installation and venting of storage tanks shall be in accordance with applications and plans approved by the commissioner and shall also meet the requirements of chapter four of this title and the rules of the fire commissioner. Except as otherwise provided for in chapter four of this title or the rules of the fire commissioner, underground tank installations shall comply with the following: (a) The tops of the tanks shall be at least two feet below finished grade and at least two feet below the level of any cellar or basement floor within ten feet of the tanks.

(b)Tanks shall be supported on foundations complying with subchapter eleven of this chapter.

(c)Tanks shall be located so that the forces from any building foundation and support loads are not transmitted to the tanks. The distance from any part of a tank to the nearest wall of any basement, pit or cellar, or from any property line that may be built upon, shall not be less than three feet.

(d)Tanks shall be covered with a structurally supported reinforced concrete slab at least eight inches thick extending at least twelve inches beyond the horizontal outlines of the tanks and placed over a coverage of suitable clean backfill material.

(e)All concrete shall have a minimum compressive strength of twenty-five hundred pounds per square inch at twenty-eight days. Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/068.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 27-440?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters