This section mandates that concealed spaces within various building structures must be firestopped to create effective draft barriers or filled with noncombustible materials. Specific requirements for materials and installation methods are outlined, with inspections required before concealment. Applies to building owners and property operators involved in construction and fire safety compliance.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-345 Firestopping.

AC § 27-345

Concealed spaces within partitions, walls, floors, roofs, stairs, furring, pipe spaces, column enclosures, etc. that would permit passage of flame, smoke, fumes, or hot gases from one floor to another floor or roof space, or from one concealed area to another, shall be firestopped to form an effective draft barrier, or shall be filled with noncombustible material in accordance with the requirements of this section. Firestopping shall not be required where a concealed space is sprinklered in accordance with the construction provisions of subchapter seventeen of this chapter, or is constructed as a shaft.

(a)Firestopping materials. In buildings of construction group I, firestopping or fill shall be of noncombustible material that can be shaped, fitted, and permanently secured in position. In buildings of construction group II, firestopping may be of combustible material consisting of wood not less than two inches nominal thickness with tight joints, two layers of one inch nominal thickness assembled so that there are no through joints or of one-half inch exterior type plywood with joints backed, except that noncombustible firestopping shall be used in concealed spaces of fire divisions and where in contact with fireplaces, flues, and chimneys. Noncombustible firestopping may be masonry set in mortar, concrete, three-quarter inch thick mortar or plaster on noncombustible lath, plasterboard at least three-eighths of an inch thick, fire-rated wallboard at least five-eighths of an inch thick, sheet metal at least No. 14 U.S. std. gage thick, solid web metal structural members, asbestos-cement board at least one-quarter of an inch thick, or equivalent rigid noncombustible material. Mineral, slag, or rockwool may be used for firestopping when compacted to a density of at least three and one-half pounds per cubic foot into a confined space of least dimension not more than one-third its second dimension.

(1)The performance of through-penetration fire stops shall be measured and specified according to reference standard RS 5-19.

(2)The commissioner may accept reference standard RS 5-19 test data results from an independent laboratory acceptable to the commissioner pursuant to subdivision (c) of section 27-131, when such data is submitted by a registered architect or licensed professional engineer to justify the usage of fire stops or the details of their installation not specified herein.

(b)Hollow partitions and furred spaces. All hollow partitions and furred out spaces shall be firestopped at each floor level. Firestops shall be the full thickness of the hollow space or furred out space.

(c)Stairs. Concealed spaces within stair construction shall be firestopped between stringers at the top and bottom of each flight of stairs so as not to communicate with concealed spaces in the floor, roof or intermediate landing construction.

(d)Ceiling spaces. Floor or roof assemblies required to have a fire-resistance rating shall have any concealed spaces therein firestopped in accordance with section 27-327 of this subchapter.

(e)Exterior cornices. Exterior cornices and eaves, constructed of combustible materials or with combustible framing, shall be firestopped at the ends of fire divisions and party walls, and at maximum intervals of twenty feet. If not continuous, they shall have closed ends and at least four inches separation between adjoining sections.

(f)Trim and finish. Where combustible trim and finish is permitted all hollow spaces shall be firestopped at ten foot intervals or shall be solidly filled with noncombustible materials.

(g)Duct and pipe spaces. Ducts and pipes enclosed in construction that does not meet the requirements of this code for shaft construction shall be firestopped at every floor level.

(h)Inspection of firestopping. The installation of all required firestopping shall be subject to the controlled inspection requirements of section 27-132 of article seven of subchapter one of this chapter, except that the architect or engineer need not be retained by the owner. Firestopping shall not be concealed from view until inspected.

Common Questions

Our team

Meet the people you will work with

TI

Tiffany Irizarry

Legal Coordinator

OATH / DOB
TI

Tiffany Irizarry

Legal Coordinator

OATH / DOB

Free case review

Have a matter that touches § 27-345?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

reception@nacmiaslaw.com

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters