This section mandates the construction of fire separations between different tenancies using materials that meet specified fire-resistance ratings. It requires that these separations maintain a minimum one-hour fire-resistance rating and extend through concealed spaces in the building's floor or roof. Applies to building owners with multiple tenancies.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-341 Fire separations.

AC § 27-341

Fire separations shall be constructed of materials or assembly of materials having at least the fire-resistance ratings required by table 5-1.

(a)Different tenancies. Different tenant apartments, suites, stores, offices, or other spaces that are not separated from each other by fire divisions, shall be separated from each other by fire separations having at least the fire-resistance rating prescribed in table 5-1, but in no case less than one hour, and shall continue through any concealed spaces of the floor or roof construction above.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 27-341?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters