Brooklyn since 2014All five boroughsSame-day response during business hours

What is NYC PC § 608.15.1?

Quick Answer

This section mandates the protection of openings and outlets by an air gap between the opening and the fixture flood level rim, as specified in Table 608.15.1. It details minimum required air gaps for various fixtures based on their effective openings. Applies to building owners responsible for plumbing installations.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

608.15.1 Protection by air gap.

PC § 608.15.1

Openings and outlets shall be protected by an air gap between the opening and the fixture flood level rim as specified in Table 608.15.1. Openings and outlets equipped for hose connection shall be protected by means other than an air gap. Table 608.15.1Minimum Required Air Gaps FixtureMinimum Air GapAway from a Wall a(inches)Close to a Wall(inches)Lavatories and other fixtures with effective openings not greater than 1/2 inch in diameter1 1 1/2 Sinks, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch in diameter1 1/2 2 1/2 Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter2 3 Drinking water fountains, single orifice not greater than 7/16 inch in diameter or multiple orifices with a total area of 0.150 square inch (area of circle 7/16 inch in diameter)1 1 1/2 Effective openings greater than 1 inchTwo times the diameter of the effective opening Three times the diameter of the effective opening For SI: 1 inch = 25.4 mm, 1 square inch = 645 mm2. a. Applicable where walls or obstructions are spaced from the nearest inside-edge of the spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 608.15.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters