What is NYC FC § 904.6.6.1?

Quick Answer

This section mandates that the quantity and pressure of extinguishing agent containers be checked at least semiannually. If a container exhibits a weight loss exceeding 5 percent or a pressure loss over 10 percent, it must be refilled or replaced. Applies to property operators maintaining fire safety equipment.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

904.6.6.1 Containers.

FC § 904.6.6.1

The extinguishing agent quantity and pressure of containers shall be checked at least on a semiannual basis. Where a container shows a loss in original weight of more than 5 percent or a loss in original pressure (adjusted for temperature) of more than 10 percent, the container shall be refilled or replaced. The weight and pressure of the container shall be recorded on a tag attached to the container.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 904.6.6.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters