This section outlines the requirements for abort systems in fire safety protocols. It specifies that these systems can only be installed on smoke detector-activated systems and details the operation of abort controls, including manual activation and alarm transmission. Applies to building owners implementing fire safety measures.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

904.3.7.2.3 Abort systems.

FC § 904.3.7.2.3

Abort systems may be installed only on systems activated by smoke detectors. Abort controls shall be manually operated, shall be located in the protected area, and shall cause the discharge of the clean agent after a 2-minute delay unless the abort control is reactivated for another cycle of delay. A manual pull station shall be provided which, upon activation, shall transmit an alarm to an approved central station, override the delay and cause the clean agent to discharge immediately. Abort controls shall not interfere with transmission of local alarms or central station alarms.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 904.3.7.2.3?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters