6404.1.4 Separation from incompatible materials.
FC § 6404.1.4
In addition to the requirements of FC 5003.9.8, indoor storage of pyrophoric materials shall be isolated from incompatible hazardous materials by 1-hour fire barriers with openings protected in accordance with the construction codes, including the Building Code. Exception: Storage in approved hazardous materials storage cabinets constructed in accordance with FC 5003.8.7.