6304.1.2 Distance from detached storage buildings to exposures.
FC § 6304.1.2
In addition to the requirements of the construction codes, including the Building Code, detached storage buildings shall be located in accordance with FC Table 6304.1.2. FC Table 6304.1.2Oxidizer (Liquids and Solids) – Distance from Detached Storage Buildings and Outdoor Storage Areas to Exposures Oxidizer ClassWeight(pounds)Minimum Distance to Buildings, Lot Lines, Public Streets, Private Roads or Building Exits (feet)Oxidizer ClassWeight(pounds)Minimum Distance to Buildings, Lot Lines, Public Streets, Private Roads or Building Exits (feet)1Note aNot Required2Note a353Note a504Up to 1050greater than 10up to 10075greater than 100up to 500100greater than 500up to 1,000125greater than 1,000up to 3,000200greater than 3,000up to 5,000300greater than 5,000up to 10,000400over 10,000As required by the commissioner For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg. a. Any quantity over the amount required for detached storage in accordance with FC 5003.8.2, or over the outdoor maximum allowable quantity for outdoor control areas.