6103.2.1.4 Group E and I occupancies.
FC § 6103.2.1.4
Portable LPG containers shall not be allowed in Group E and I occupancies, except as set forth in this section and the rules. In Group E and I occupancies, portable LPG containers are allowed to be used for research purposes. Such containers shall not be used in classrooms. Such containers shall not exceed 16.4 ounces (0.465 kg) of LPG. Where more than one such container is present in the same room, each container shall be separated from other containers by a distance of not less than 20 feet (6096 mm).