608.9.4.1.4 Control areas.
FC § 608.9.4.1.4
Indoor systems shall be installed only in control areas designed, installed, operated and maintained in accordance with this section. The maximum aggregate rated energy capacity of indoor systems per control area shall be in accordance with FC 608.9.1. The design and number of control areas per floor shall be in accordance with FC 5003.8.3.3, including FC Table 5003.8.3.3, except that (subject to FC 608.9.4.1.9 and FC 608.9.4.1.10) each control area housing an indoor stationary energy storage system shall be designed and constructed as a high-hazard occupancy, and rooftop installations shall be treated as outdoor installations.