608.9.4.1.2 Sprinkler protection required.
FC § 608.9.4.1.2
Indoor systems may be installed only in buildings fully protected throughout by a sprinkler system, except as otherwise provided in FC 608.9.4.1.9. Control areas housing stationary energy storage systems shall be fully protected throughout by a sprinkler system designed in accordance with NFPA 15, except as may otherwise be approved based on equipment listings and testing results pursuant to FC 608.4.