This section regulates the height and operation of makeup air openings in buildings, stipulating that they cannot be higher than 6 feet above floor level. It also specifies the minimum gross area for makeup air inlets based on smoke exhaust requirements. Applies to building owners managing ventilation systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

910.4.3.1 Makeup air.

BC § 910.4.3.1

No portion of the makeup air openings shall be higher than 6 feet (1828.8 mm) above the floor level. Operation of makeup air openings shall be manual or, if properly coordinated with the smoke removal system, automatic. The minimum gross area of makeup air inlets shall be 8 square feet per 1,000 cubic feet per minute (0.74 m 2 per 0.4719 m 3 /s) of smoke exhaust.