What is NYC BC § 909.11.1?

Quick Answer

This section mandates that standby power sources be housed in a dedicated room separate from normal power transformers and switch gears, with direct ventilation to the exterior. The room must be enclosed with fire barriers or fire-resistance-rated assemblies. Applies to building owners responsible for electrical installations.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

909.11.1 Equipment room.

BC § 909.11.1

The standby power source shall be located in a room separate from the normal power transformers and switch gears, and ventilated directly to and from the exterior. The room shall be enclosed with not less than 2-hour fire barriers constructed in accordance with Section 707, or with not less than 2-hour fire-resistance-rated horizontal assemblies constructed in accordance with Section 711, or both.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 909.11.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters