907.2.8.3 Smoke detectors within dwelling units and sleeping units.
BC § 907.2.8.3
Smoke detectors and audible notification appliances shall be installed in dwelling units and sleeping units and shall be annunciated by dwelling unit and sleeping unit at a constantly attended location from which the fire alarm system is capable of being manually activated. Smoke detectors are required in the following areas: 1. In sleeping areas.
2.In every room in the path of the means of egress from the sleeping area to the door leading from the dwelling unit and sleeping unit.
3.In each story within the unit, including below-grade stories. For dwelling units and sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level.