907.2.12.1 Alarm.
BC § 907.2.12.1
Actuation of a single smoke detector, automatic sprinkler system or other automatic fire detection system shall initiate a pre-signal system in accordance with NFPA 72 at a constantly attended location from which the Fire Department shall be notified and live voice evacuation instructions shall be initiated using an emergency voice/alarm communications system in accordance with Section 907.5.2.2.