903.2.9 Group S-1.
BC § 903.2.9
An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where any one of the following conditions exists: 1. A Group S-1 fire area exceeds 12,000 square feet (1114.8 m 2 ).
2.The building is greater than 1,000 square feet (92.9 m 2 ) in area and the main use or dominant occupancy is Group S-1.
3.A Group S-1 fire area is located more than three stories above grade plane.
4.The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2229.7 m 2 ).
5.A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464.5 m 2 ).
6.A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232.3 m 2 ).