What is NYC BC § 903.2.7.2?

Quick Answer

This section mandates the installation of an automatic sprinkler system in any Group M occupancy fire area that exceeds 7,500 square feet or contains an unenclosed stair or escalator connecting multiple floors. Applies to building owners of Group M occupancies.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

903.2.7.2 Group M fire areas.

BC § 903.2.7.2

An automatic sprinkler system shall be provided throughout any Group M occupancy fire area where any one of the following conditions exists: 1. The fire area exceeds 7,500 square feet (696.8 m 2 ).

2.The fire area of any size contains an unenclosed stair or escalator connecting two or more floors. (Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023) Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.