This section mandates the installation of an automatic sprinkler system in buildings with Group F occupancy under specific conditions, such as exceeding certain square footage or height requirements. The statute is enforced by the Department of Buildings (DOB). Applies to building owners of Group F-1 fire areas.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

903.2.4 Group F.

BC § 903.2.4

An automatic sprinkler system shall be provided throughout all buildings containing a Group F occupancy where any one of the following conditions exists: 1. Where a Group F-1 fire area exceeds 12,000 square feet (1114.8 m 2 ); 2. Where a Group F-1 fire area is located more than three stories above grade plane; 3. Where the combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2229.7 m 2 ); 4. Where required by Section 280 of the New York State Labor Law for "factory buildings" defined in Section 2 of such law; or 5. Where a Group F-1 occupancy used for the manufacture of upholstered furniture or mattresses exceeds 2,500 square feet (232.3 m 2 ).

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 903.2.4?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters