This section outlines the calculation for determining the total fire-resistance rating of multi-wythe walls with an airspace. The formula provided includes variables for the fire-resistance of individual wythes and a coefficient for the airspace. Applies to building owners involved in the construction or renovation of multi-wythe walls.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

722.4.1.3 Multi-wythe walls with airspace.

BC § 722.4.1.3

Where a continuous airspace separates multiple wythes of the wall or partition, the total fire-resistance rating shall be determined by the formula: R = (R 10.59 + R 20.59 + . . . + R n0.59 + as) 1.7 (Equation 7-10) where: R = The fire-resistance of the assembly (hours). R 1 , R 2 and R n = The fire-resistance of the individual wythes (hours). as = Coefficient for continuous airspace. Values for R n0.59 for use in Equation 7-10 are given in Table 722.4.1(3). The coefficient for each continuous air-space of 1/2 inch to 3 1/2 inches (12.7 to 89 mm) separating two individual wythes shall be 0.3.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 722.4.1.3?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters