What is NYC BC § 716.5.9.3?

Quick Answer

This section mandates that automatic-closing fire doors in specified locations must close automatically when smoke detectors are activated or lose power. The doors must not have more than a 10-second delay before closing. Applies to building owners with fire safety compliance responsibilities.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

716.5.9.3 Smoke-activated doors.

BC § 716.5.9.3

Automatic-closing fire doors installed in the following locations shall be automatic-closing by the actuation of smoke detectors installed in accordance with Section 907.3 or by loss of power to the smoke detector where such detector is powered by the building's normal electrical service or by loss of power to the hold-open device. Doors that are automatic-closing by smoke detection shall not have more than a 10-second delay before the door starts to close after the smoke detector is actuated.

1.Doors installed across a corridor.

2.Doors installed in the enclosures of exit access stairways and ramps in accordance with Sections 1019 and 1023, respectively.

3.Doors that protect openings in exits or corridors required to be of fire-resistance- rated construction.

4.Doors that protect openings in walls that are capable of resisting the passage of smoke in accordance with Section 509.4.

5.Doors installed in smoke barriers in accordance with Section 709.5.

6.Doors installed in fire partitions in accordance with Section 708.6.

7.Doors installed in a fire wall in accordance with Section 706.8.

8.Doors installed in shaft enclosures in accordance with Section 713.7.

9.Doors installed in refuse and laundry chutes and access and termination rooms in accordance with Section 708.13.

10.Doors installed in waste and linen chutes, discharge openings and access and discharge rooms in accordance with Section 713.13. Loading doors installed in waste and linen chutes shall meet the requirements of Sections 716.5.9 and 716.5.9.1.1.

11.Doors installed in the elevator lobby walls of underground buildings in accordance with Section 405.4.3.

12.Doors installed in smoke partitions in accordance with Section 710.5.2.3.

13.Doors serving interior exit stairways or ramps in accordance with the exception to Section 713.7.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 716.5.9.3?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters