This section outlines the labeling requirements for smoke and draft control doors that comply with UL 1784. The doors must display the letter 'S' on the fire rating label to indicate compliance with gasketing installation standards. Applies to manufacturers and installers of smoke and draft control doors.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

716.5.7.3 Smoke and draft control door labeling requirements.

BC § 716.5.7.3

Smoke and draft control doors complying with UL 1784 shall be labeled in accordance with Section 716.5.7.1 and shall show the letter "S" on the fire rating label of the door. This marking shall indicate that the door and frame assembly are in compliance where listed or labeled gasketing is installed.