What is NYC BC § 716.5.3.1?

Quick Answer

This section outlines the requirements for fire door assemblies regarding smoke and draft control, mandating compliance with UL 1784 testing standards. The air leakage rate must not exceed specified limits, and louvers are prohibited. Applies to building owners responsible for fire safety compliance in their properties.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

716.5.3.1 Smoke and draft control.

BC § 716.5.3.1

Fire door assemblies shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784. The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot (0.01524 m 3 /s · m 2 ) of door opening at 0.10 inch (24.9 Pa) of water for both the ambient temperature and elevated temperature tests. Louvers shall be prohibited. Installation of smoke doors shall be in accordance with NFPA 105.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 716.5.3.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters