715.6 Fire-resistant joint systems in smoke barriers.
BC § 715.6
Fire-resistant joint systems in smoke barriers, and joints at the intersection of a horizontal smoke barrier and an exterior curtain wall, shall be tested in accordance with the requirements of UL 2079 for air leakage. The L rating of the joint system shall not exceed 5 cfm per linear foot (0.00775 m 3 /s m) of joint at 0.30 inch (7.47 Pa) of water for both the ambient temperature and elevated temperature tests.